M310 Series MPO (MTP) 144 Core Singlemode Fibre Trunk Cables

Data Centre Fibre Cables - Light Flexible Small Bend Radius

Part Number M312-EFEF-144LS-S-NS-XXX-C
Polarity C (standard). A and B available
Fibre Type OS2 (9 / 125)
Fibre Capacity 144
Glass Fibre Corning Clearcurve®
Fibre Construction Dry loose tube micro cable LSZH
Cable Diameter 15.5mm +/- 0.5mm
End 1 MTP® ELITE 12 Fibre Connector (x12)
End 2 MTP® ELITE 12 Fibre Connector (x12)
Insertion Loss across cable < 0.35 dB + cable loss
Product Warranty 25 year fully covered

M310 Series MTP® trunk cables form the backbone to the M Series solution. They are designed for a tool-less installation with MX and M310 modular cassettes or MX and M310 couplers and utilise Click-2-Connect® technology for a fast and simple way to grow the network.

MPO MTP® ELITE® low loss connectors with level 6 multistage termination

MTP® trunk cables use a lightweight but robust micro core fibre cable and MTP® connectors. They are about 65% lighter and 60% smaller in diameter than traditional tight buffered or loose tube fibre and gives the ability to install more fibre into less space. All trunk cables have a full lifetime guarantee and are protected by the Complete Connect warranty. Every trunk cable is supplied with a full test certificate and is traceable though a unique serial number.

Complete Connect are MPO MTP Specialists with 40+ years experience. Learn more About Us.

Technical Drawings

M310 Series MTP Trunk Cable with Single Sheath

144 fibre mtp 10G data centre trunk cable
144 fibre micro core loose tube cable

To ensure the best performance, use a recognised MTP Connector and QSFP + Port Cleaning Tool

MPO MTP Cleaning Tool
Optical Performance And Physical Specifications
MPO (MTP) Singlemode OS2 12 Fibre Connector
Connector Housing Yellow
Ferrule MT ELITE
Typical Insertion Loss 0.10 dB (average)
Maximum Insertion Loss 0.35 dB (Max)
MTP 12 Fibre Male Connector
144 Core Physical Specification
Single Sheath
Weight kg/Km 87
Outer diameter 15.5mm +/- 0.5mm
Inner jacket diameter 2.9mm
Sheath wall thickness 0.48mm
Maximum pull force 300 N
Transport and storage – 25 °C to + 70 °C
Installation – 20 °C to + 60 °C
Installed – 20 °C to + 60 °C
Minimum bend radius (installed) 10 x outside diameter
Minimum bend radius (installation) 20 x outside diameter
Maximum load (short term / long term) 660 / 200 N/dm
Outer / inner sheath colour Aqua / Aqua
12 Core Construction
Single Sheath
Design One hundred and forty four 250um fibres with aramid yarn strain relief
within 12 x 12 fibre sub-units
Construction Dry Loose Tube (no gel)
Sheath Properties LSZH – Halogen free, flame retardant
Application Indoor, cable trays and ducting
Fire Performance
Flame Retardancy acc. IEC 60332-1-2 and IEC 60332-3-22 Cat. A
Smoke Density acc. IEC 61034
Halogen-free acc. IEC 60754-1
Acidity of Combustion Gases acc. IEC 60754-2
Cable Design
Singlemode OS2 (9 / 125)
Optical Core 9.2μm +/- 0.4μm diameter
Optical Claddinng 125μm +/- 0.7μm diameter
Primary Acrylate Coating 242μm +/- 10 to 15μm diameter
Core Concentricity 0.5μm
Optical Performance
Singlemode OS2 (9 / 125)
Attenuation Coefficient
dB/Km (installed)
1310nm ≤ 0.36 Max
1550nm ≤0.22 Max
Attenuation Coefficient
dB/Km (un-installed)
1310nm ≤ 0.36 Max
1550nm ≤0.22 Max
1625nm ≤ 0.20 Max
Overfill Launch Minimum
Bandwidth Mhz x Km
850nm ≥ 3500
1300nm ≥ 500
 Commitment to Excellence

Complete Connect are committed to providing the highest quality performing products. This is achieved through

  • Sourcing the best components
  • Utilising the lastest fibre termination technology
  • Maintaining rigorous processes

LC: IEC-61754-20
SC: IEC-61754-14
IEC-60793

Cable Standards

TIA/EIA-568-C.3 and ISO/IEC 11801

Connector Standard

MPO: IEC-61754-7, EIA/TIA-604-5
Compliant to Directive 2002/95/EC (RoHS) and REACH SvHC

Further Information

Compatibility with LC cassette modules

  1. M310 trunk cables offer instant connectivity when used with M310 LC modular cassettes
  2. M310 trunks are compatible with other MTP based systems such as Panduit, Corning, Siemon plus many others
  3. The MTP trunks can have either male or female connectors
  4. There are 3 types of cable polarity: A, B or C. Complete Connect will ensure the correct polarity is provided.
  5. All Complete Connect cables use the MT Elite ferrule within the MTP fibre connector. This provides the best optical connection possible.

Maximum transmission distances

  1. The IEEE standard states maximum distances based on loss budgets for OM3, OM4 and singlemode transmission.
  2. Distances vary depending on a number of factors including no. of mated connector pairs and cable routing.
  3. Complete Connect’s technical team can provide all the relevant information concerning loss budgets and allowable distances.

Testing using Loopback adaptor cables

  1. MTP loopback cables can be used to test individual trunk cables.
  2. LC loopback adaptors can be used to test full channels.